Skip to content
Industrial gas detection for demanding environments

technical guide

How to Plan a Fixed Gas Detection System

A fixed gas detection system is a set of detectors at chosen points, a place where their signals end up (an alarm controller, a DCS or both), an agreed signal type for each point, and the outputs that act on an alarm. Plan it in this order: count channels by gas, pick the signal, then size the controller, wiring and power.

How many channels does a fixed gas detection system need?

One per gas, not one per detector. Eranntex controllers are sized in gas channels, so a detector that measures four gases uses four channels whichever way it is wired.

Drawing of a fixed gas detection system on a mounting board: a single-gas detector on a 4–20 mA loop and a four-gas detector on an RS485 bus run to a gas alarm controller whose relays drive a beacon, a fan and a valve actuator; an uplink cable runs to a DCS rack, and a dashed line marks a detector wired straight to the DCS.
Fig. 1. How a fixed gas detection system fits together. At the back, a single-gas detector on a 4–20 mA loop (black cable) and a four-gas detector on an RS485 bus (orange cable) run to the gas alarm controller; its relay terminals drive the beacon, fan and valve actuator in front; an uplink cable runs to the DCS rack on the right, and the dashed line marks a detector wired straight to the DCS. Concept drawing, not a wiring or installation layout.

The wiring changes how those channels arrive. On 4–20 mA, a multi-gas detector such as the GTYQ-MIC-600 gives one analog loop per gas, so a four-gas unit needs four analog inputs and is ordered with four analog output channels. On RS485 the same detector uses one pair of wires and one Modbus address, and sends all four readings and alarm states over it. The controller still manages those as four channels.

Six four-gas detectors therefore make 24 channels. Wired on 4–20 mA they need 24 analog inputs, which only the MIC-1000 and MIC3000 offer. On RS485 they take six addresses and fit within any of the four MIC controllers.

Channel capacity is not the only thing that sets the number of controllers; the site layout does too. On one chemical-plant project, 98 single-gas CO detectors were spread over 16 explosion-protected MIC2000-Ex controllers on RS485. Most controllers served a dozen or so detectors in one area; some served a single detector. None was close to its 128-input limit.

4–20 mA or RS485: which signal for each point?

All five Eranntex fixed detectors provide three-wire 4–20 mA and RS485 Modbus RTU as standard, and all four MIC controllers accept both, so any of these detectors can be paired with any MIC controller on either signal. Eranntex handles combinations outside the published outputs as custom development.

4–20 mA and RS485 Modbus RTU compared
Aspect4–20 mARS485 Modbus RTU
Wires per detectorOne loop per gasOne shared bus pair for many detectors
What it carriesLive concentration over the 0–100% range; fault and over-range shown as defined currents below 4 mA or above 20 mALive concentration, low and high alarm states and fault state for every gas
Where alarm limits sitUsually in the DCS, or in the controller's relay logicIn the detector and controller; the DCS reads the states
Typical useDirect input to a DCS or PLC analog cardMany points on one cable to a MIC controller, or to a DCS over Modbus

Eranntex detectors use one factory-default set of fault and over-range current values across the range. The values are given in the technical documents and can be changed at order to match a DCS analog input configuration. A broken loop is a separate case: the current falls to near zero, so the input card sees a wiring fault rather than a detector status.

For Modbus integration, Eranntex supplies the register map for the specific controller or detector model with the shipment, or earlier on request when the DCS is being configured during design. It is not a public download because it has to match the hardware and firmware version.

HART is optional on all five detectors: HART 5 on the GTYQ-MIC-500S and GTYQ-MIC-600, HART 5 or HART 7 on the GTYQ-MIC-500S-CB-IR2, and HART on the MIC-500S-CB and MIC-600-CB. It is used with a DCS or a handheld communicator; the MIC controllers do not list HART as an input.

Decide where the alarm acts

Eranntex supports four arrangements, and the choice depends on who has to react to an alarm:

  • Detectors to a MIC controller, with local actions. The controller drives beacons, fans or valves from its relays.
  • Detectors to a MIC controller, then to a DCS or plant network. The controller handles local alarms and passes data upward over RS485 Modbus, or over optional 4–20 mA, Ethernet or wireless outputs.
  • Detectors straight to a DCS. No Eranntex controller is used; the DCS reads 4–20 mA or Modbus.
  • A mix. Some points go to a MIC controller and some go directly to the DCS.

Every MIC controller sets low and high alarm limits separately for each channel, has three alarm levels, and can link each channel to up to three relay outputs. The relays are programmable, so one detector can start a fan at the first level and close a valve at the second. The controllers also check each input line for open and short circuits.

Each detector has its own dry-contact relays: up to two on the MIC-500S models and MIC-600-CB, up to three on the GTYQ-MIC-600. These can switch a local beacon even where the signal goes straight to a DCS.

Field example: ammonia alarms on refrigerated fishing vessels

Cut-away drawing below deck on a refrigerated fishing vessel: ammonia detectors on the shell wall of the freezer holds and the compressor space run their cables through a covered tray to one MIC3000 controller on a pedestal, which switches the ventilation fan and the sprinkler solenoid valve over the compressor.
Fig. 2. Ammonia alarms on a refrigerated fishing vessel, shown as a cut-away section below deck. Detectors on the shell wall of the freezer holds and the compressor space send their cables (orange) through a covered tray to one MIC3000 controller, which switches the ventilation fan and the solenoid valve of the sprinkler line over the compressor. Concept drawing of one project; the number and position of detectors in each hold are not shown.

Each vessel in the batch had five freezer holds and a compressor space to watch, with fans and a sprinkler system to be switched on alarm. Each received single-gas ammonia detectors on RS485 and one MIC3000. The customer's specification had asked for 0–1000 ppm everywhere. Eranntex engineers set the freezer holds to 0–100 ppm, because the risk there is exposure of people entering the hold, and the compressor space to 0–100 %LEL, with the low alarm at 20 %LEL starting the sprinklers through a controller relay. Each detector was wired with a twisted pair for RS485 and a two-core power cable. Power-loss cover was left to the vessels' own UPS because the hold time had not been defined. The shipyard's contractor installed the system with remote guidance from Eranntex.

How to size the alarm controller

Start with where the controller will be mounted. The MIC-1000-Ex and MIC2000-Ex are explosion-protected and designed to sit in the hazardous area itself, for example on a skid or tank farm without a control room. Where a safe-area control room exists, Eranntex recommends a standard controller there: it costs less, and opening it for adjustment does not need a hazardous-area work permit.

Capacity then decides the model. All four take 4–20 mA and RS485 inputs at the same time.

MIC gas alarm controllers: inputs, relays and backup power
ControllerMounting4–20 mA inputsRS485 inputsRelays (standard / optional)Backup power
MIC-1000Wall, safe area1–8, 16, 24 or 32Up to 1284 + 1 common / 8, 12, 16, 24 or 3212 V DC, 7 Ah, standard
MIC-1000-ExWall, explosion-protected1–8Up to 1284 + 1 common / 8, 16, 24 or 3224 V DC, 5 Ah, optional
MIC2000-ExWall, explosion-protected1–8Up to 1284 + 1 common / 8, 16, 24 or 3224 V DC, 5 Ah, optional
MIC3000Wall, safe area, 9-inch touchscreen1–8, 16, 24 or 32Up to 256; cascaded systems up to 1000 input channels8 + 1 common / 16, 24 or 3224 V DC, 5 Ah, optional

Standard relay contact ratings:

  • MIC-1000, MIC-1000-Ex and MIC2000-Ex: 3 A at 32 V DC or 3 A at 220 V AC; common alarm output 12 A at 32 V DC or 7 A at 240 V AC.
  • MIC3000: 3 A at 250 V AC or 3 A at 30 V DC; common alarm output 10 A at 277 V AC or 12 A at 125 V AC.
  • Relay assignment and ratings can be customized for a project.

The 128 and 256 figures are the most channels one controller can manage. When a project mixes analog and RS485 inputs, the usable split depends on detector types, bus loading and polling time, so Eranntex sets the channel allocation from the project's point list and pre-commissions the controller before shipment.

Wiring, power and the hazardous-area interface

Wiring and bus loading

Eranntex engineers usually wire an RS485 detector with one four-core cable: two cores for the 24 V DC supply and two for the RS485 pair, so each run is pulled once. On a multi-building laboratory project this replaced an initial plan of two separate two-core cables.

Electrical loading limits one RS485 bus to about 32–64 detectors in Eranntex practice; larger systems use more bus loops on the controller or RS485 repeaters and hubs. Each detector on a bus needs a unique address from 1 to 128 and the same baud rate as the controller. Addresses can be set through the menu with the infrared remote, and on the CB models also with a magnetic wand, without opening the enclosure. Send a tag list with the order and Eranntex pre-sets the addresses at the factory.

Power

The MIC-1000 is specified at 2.5 W per input and can power all 32 analog detectors from its internal supply, which covers typical electrochemical and catalytic detectors. A separate 24 V DC supply near the detectors is worth adding in three cases:

  • cable runs beyond roughly 300–500 m, where voltage drop can leave the detector under-supplied;
  • RS485 buses with many detectors, powered in segments while the controller carries only the communication pair;
  • sites that need long operation after a mains failure, since the controller's backup battery has limited hold time at full load.

Hazardous-area interface

When detectors sit in a hazardous area and the controller in a safe area, Eranntex recommends fitting a safety barrier or isolating barrier on the safe-area side of each detector circuit, and its engineers size it from the area classification and the detector model before shipment. For an intrinsically safe circuit, such as the RS485 circuit covered by the intrinsic-safety parameters in the GTYQ-MIC-600 certificate, the barrier is part of the certified system and is always fitted. For other circuits, whether it is fitted depends on site conditions.

Drawing of a hazardous area marked on the floor: a flameproof detector, a detector with an intrinsically safe RS485 circuit and an explosion-protected controller run cables through a curb transit to an open safe-area cabinet, where they land on an isolator, an intrinsic-safety barrier and a terminal block before the controller.
Fig. 3. Detectors in a hazardous area (tinted floor) wired to a safe-area cabinet. A flameproof detector, a detector with an intrinsically safe RS485 circuit (orange) and an explosion-protected controller run their cables through a transit in the curb; inside the open cabinet they land on an isolator, an intrinsic-safety barrier (orange) and a terminal block before the controller on the back panel. Concept drawing; barrier selection follows the area classification, detector model and certificate.

The detector's certificate states its protection type: the GTYQ-MIC-500S family is flameproof (Ex db IIC T6 Gb), and the GTYQ-MIC-600 is certified Ex da ia IIC T6 Ga under CE24.5822X, whose annex includes intrinsic-safety parameters for its RS485 circuit.

For sensing principle and mounting position on oil and gas sites, see the oil and gas page. For whether a project needs fixed monitoring at all, start with How to Define an Industrial Gas Leak Detection Project.

What to send with an enquiry

A point list lets Eranntex size the controller, relays and power in one pass. For each point, the useful columns are:

Enquiry worksheet

Point list for a fixed gas detection system

Gas-by-gas enquiry worksheet
Tag or locationGasMeasuring rangeSignal (4–20 mA / RS485 / HART)Hazardous-area zone

Entries stay in this page. Preparing text does not submit an enquiry.

Use one row for each gas at each point.

Models: fixed gas detectors · gas alarm controllers · Request a quote

Frequently asked questions

Yes. All five models provide three-wire 4–20 mA and RS485 Modbus RTU as standard, with HART as an option. Each detector's own relays can still drive a local beacon.
Yes for 4–20 mA detectors. For RS485, the detector must use Modbus RTU, and its register map has to be supplied before shipment so the controller can be set up for it.
When the cable run is longer than roughly 300–500 m, when many detectors share one RS485 bus, or when the system must keep running for a long time after a mains failure. Otherwise the MIC controller can power the detectors directly.

Products for further evaluation

Angled front view of the Eranntex MIC-3000 industrial wireless gas alarm controller cabinet with high-resolution touchscreen display, multi-channel LED matrix, and lockable front door.
Certificates & documents (2)

MIC3000

MIC3000 Gas Alarm Controller

A high-capacity gas alarm controller for centralized monitoring, alarm management and system integration.

Controller inputs
1 channel of 4–20 mA input standard; expandable to 32 channels, with up to 256 RS485 inputs; cascaded systems support 1000 input channels
Output
RS485 Modbus standard; 4–20 mA, 4G, 433 MHz, LoRa, Zigbee and Ethernet outputs are optional
Relays
Eight control relay groups plus one common output standard; 16, 24 or 32 control groups optional
Mounting
Wall mounted
Eranntex MIC-1000 product view.
Certificates & documents (3)

MIC-1000

MIC-1000 Gas Alarm Controller

A wall-mounted gas alarm controller for integrating analog and RS485 field detectors.

Controller inputs
1 channel of 4–20 mA input standard; expandable to 32 channels, with up to 128 RS485 inputs
Output
RS485 Modbus standard; 4–20 mA, 4G, 433 MHz, LoRa, Zigbee and Ethernet outputs are optional
Relays
Four control relay groups plus one common output standard; expanded relay configurations are optional
Mounting
Wall mounted